Description
Certification RCM compliance mark c UL us – Recognized (OL) CE marking (see declaration of conformity) As per EU EMC directive As per EU rohs directive KC characters KC EMC Certificate issuing authority UL E322346 UL E322346 Note on materials rohs-compliant Measured variable Flow rate Consumption Flow direction Unidirectional P1 -> P2 Measuring principle Thermal Flow measuring range start value 6 l/min Flow measuring range end value 600 l/min Operating pressure 0 bar … 10 bar Operating medium Compressed air as per iso 8573-1:2010 [7:4:4] Nitrogen Temperature of medium 0 °c … 50 °c Ambient temperature 0 °c … 50 °c Nominal temperature 23 °c Accuracy of flow rate ± (3% o.m.v. + 0.3% FS) Zero point repetition accuracy in ± %FS 0.2 %FS Repetition accuracy margin in ± %FS 0.8 %FS Switching output 2 x PNP or 2 x NPN switchable Switching function Window comparator Threshold value comparator Switching element function N/C contact N/O contact Max. output current ≤100 mA Analog output 0 – 10 V Flow characteristic curve, start value 0 l/min Flow characteristic curve, end value 600 l/min Output characteristic curve initial value 0 V End value output characteristic curve 10 V Min. load resistance of voltage output 10 kOhm Short-circuit protection yes DC operating voltage range 15 V … 30 V Reverse polarity protection for all electrical connections
Electrical connection 5-pin
M12x1
Plug, straight
Pin allocation in accordance with standards EN 60947-5-2
Type of mounting Optionally:
With through-hole
With H-rail
With wall/surface bracket
Mounting position Any
Pneumatic connection QS-10
Product weight 600 g
Housing material PA-reinforced
Display type Illuminated LCD blue
Displayable unit(s) l
l/min
m3
scf
scf
scfm
Degree of protection IP65
Pressure drop <100 mbar
Corrosion resistance class (CRC) 2 - Moderate corrosion stress
Additional information
series | Air Flow Sensors, Sensors |
---|